UL Listed Withstand and Close-On Ratings - ASCO Series 300 |
||
Switch Rating amps |
Available Symmetrical Amperes - RMS at 600 VAC |
|
When Used With Current Limiting Fuses |
When Used With Specific Circuit Breakers |
|
30 |
100,000 |
10,000 |
70, 100, 104, 150 |
200,000 |
22,000 |
200 (240 V Max.) |
200,000 |
22,000 |
225, 260, 400 |
200,000 |
42,000 |
600, 800, 1000, 2000 |
200,000 |
65,000 |
1600, 2000 |
200,000 |
85,000 |
2600, 3000 |
200,000 |
100,000 |
Ordering Codes - ASCO Series 300 & 386 |
|||||||||||
To order an ASCO Series 300 or 386 Transfer Switch, complete the catalog number as shown. |
|||||||||||
300 + B + 3 + 600 + N + 1 + X + C + 11BG + 480 V 60 Hz |
|||||||||||
Continuous Rating |
|
Enclosure | |||||||||
Blank | Open Type | ||||||||||
300 | B | 3 | 600 | N | 1 | X | 11BG | 480 V 60 Hz | |||
300
|
Blank Solid Neutral
B1 Switched Neutral
|
2 poles,
3
poles, 3 phase
|
30, 70, 104, 150, |
1 |
Insert "X"
|
or Blank |
11BG |
Volt & Freq This information is necessary to allow correct control settings prior to shipment. |
|||
C |
Standard Enclosure |
||||||||||
Auxiliary Contacts (2 Sets max) |
|||||||||||
Strip Heater with Thermostat |
|||||||||||
Serial Interface Module |
|||||||||||
M |
Type 3R Secure Enclosure |
72E |
|||||||||
Note:
|
Copyright © 1996-2016 GeneratorJoe Inc. & GeneratorJoe®. All Rights Reserved. - © Copyright 1996-2016 ASCO Power Technologies