Time Delay |
2C An extended time delay on engine starting. Adjustable from 0 to 60 min in 1 second steps. Factory set at 5 minutes. |
|
Manual Controls for Automatic Transfer Switches |
6C Reset switch for manual retransfer to normal with automatic retransfer in the event of emergency source failure. |
6D Selector switch for automatic/manual retransfer to normal. Automatic bypass if emergency fails. |
|
Engine Generator Controls and Accessories |
12
Three position engine control selector switch.
Positions: 1 - Stop 2 - Automatic 3 - Engine |
Note: Engine controls containing engine stop positions should be located at the engine generator. (Consult ASCO for application assistance). |
|
Indicators |
14A/14B Additional auxiliary contact sets to indicate switch position. Two sets are standard. Specify total number of sets if more are required. |
18B Two-pole, double-throw contacts operate when emergency source voltage is present at transfer switch terminals. |
18G
Two-pole, double-throw contacts operate when normal
source voltage is present at transfer switch
terminals |
99 Push-to-Test
feature on all pilot light indicators |
|
Customer Control Circuits |
30A Load-shedding circuit initiated by opening of a customer-supplied contact. |
30B Load-shedding circuit initiated by removal of customer-supplied control voltage. (Specify voltage). |
31Z Selective load disconnect control contacts (two provided) which operate with time delay prior to and/or after load transfer and retransfer. |
43R
Terminal block for all customer control connections
on 30-150 amp only (standard on all other sizes). |
|
Neutral Conductor Options |
Solid neutral, with fully-rated terminals. (AL-CU) UL Listed. |
Conventional neutral switching pole. |
Overlapping neutral transfer contacts. Allows for proper ground-fault sensing and avoids generator voltage transients during transfer. |
Specify
neutral option in catalog number, see page 16 for
instructions |
|
Extension Harness |
37B
Six foot (6') extension harness to increase distance
between transfer switch and control panel on
open-type units |
|
Analog Load Metering Options |
23B Three phase ammeter with selector switch (with current transformers and shorting blocks). |
24B
Three phase voltmeter with selector switch |
Notes: Refer to ASCO 7000 Series Data Monitor which provides voltage, frequency and power monitoring. |
|
Serial Communications |
72A
Serial communication module for remote
communications to ASCO Power Quest products |
|
|
Surge Protection - ASCO Pulsar 450 rated 40KA |
73AC1 Normal source protection. (3Ø, 4wire WYE) |
Emergency source protection. (3Ø, 4wire WYE)73AC2 |
Load side protection. (3Ø, 4wire WYE)73AC3 |
Other distribution voltages available (Contact ASCO). Notes: |
|
|
Bypass Isolation Switch Options |
14A1 Auxiliary contact to close in Bypass to Normal position. |
14B1 Auxiliary contact to close in Bypass to Emergency position. |
14T Auxiliary contact to close when transfer switch is in Automatic position. |
14U Auxiliary contact to close when transfer switch is in Isolate position. |
14V Auxiliary; contact to close when transfer switch is in Test position. |
|
|
ATS Bypass Isolation Drawout Features (1000-2000 amperes) |
82B Transfer switch lifting yoke to facilitate the removal of the transfer switch from the drawout carriage. |
82C Automatic shutters to provide isolation of bus stabs. |
|
Notes: An externally operable quick-make, quick-break (QMQB), manual handle is available on some 7000 Series product configurations. (Consult ASCO for guidance). |