ASCO Automatic Transfer Switch Series Feature Comparison |
||||
Feature Comparison |
185 | 300 | 4000 | 7000 |
|
||||
Intended Application
|
Residential
Light Commercial |
Commercial
Light Industrial |
Industrial
|
Mission Critical
Critical Power |
Ampere sizes
available
|
100, 200, 230
|
30 - 3,000
|
30 - 4,000
|
30 - 4,000
|
Low Voltage
|
220 - 240V
|
115 - 600V
|
115 - 600V
|
115 - 600V
|
Medium Voltage
|
N/A
|
N/A
|
N/A
|
5kV, 15kV
|
Product Type | 185 | 300 | 4000 | 7000 |
Open Transition Transfer Switch |
Yes
|
Yes
|
Yes
|
Yes
|
Service Entrance Rated Transfer Switch |
Yes
|
Yes
|
Yes
|
Yes
|
Power Transfer Load Center |
Yes
|
Yes
|
N/A
|
Yes
|
Closed-Transition Transfer Switch |
N/A
|
N/A
|
Yes
|
Yes
|
Delayed-Transition Transfer Switch |
N/A
|
N/A
|
Yes
|
Yes
|
Soft Load Transfer |
N/A
|
N/A
|
N/A
|
Yes
|
Bypass-Isolation transfer Switch |
N/A
|
N/A
|
N/A
|
Yes
|
Closed-Transition Bypass-Isolation TS |
N/A
|
N/A
|
N/A
|
Yes
|
Delayed-Transition Bypass-Isolation TS |
N/A
|
N/A
|
N/A
|
Yes
|
Soft Load Bypass-Isolation TS |
N/A
|
N/A
|
N/A
|
Yes
|
Withstand and Close-On Ratings | 185 | 300 | 4000 | 7000 |
WCR when used with any
circuit breaker
|
10kA
|
N/A
|
10-100kA
|
10-100kA
|
WCR when used with
specific circuit breakers
|
10kA
|
22-100kA
|
22-100kA
|
22-100kA
|
WCR when used with
current limiting fuses
|
100-200kA
|
100-200kA
|
100-200kA
|
100-200kA
|
Withstand Short Time
Rating
|
N/A
|
N/A
|
36-65kA
|
36-65kA
|
Neutral Configuration | 185 | 300 | 4000 | 7000 |
Solid
|
Std.
|
Std.
|
Yes
|
Yes
|
Switched
|
N/A
|
Yes
|
Yes
|
Yes
|
Overlapped
|
N/A
|
N/A
|
N/A
|
Yes
|
Voltage and Frequency Settings | 185 | 300 | 4000 | 7000 |
Phase Selection
|
Single Phase
|
Single or Three Phase
|
Single or Three Phase
|
Single or Three Phase
|
Pick up Normal Source
Voltage
|
204 Volts
|
90% or 95%
|
85 to 100%
|
85 to 100%
|
Drop out Normal Source
Voltage
|
180 Volts
|
70% to 90%
|
70 to 98%
|
70 to 98%
|
Pick up Emergency Source
Voltage
|
204 Volts
|
90% Fixed
|
85 to 100%
|
85 to 100%
|
Drop out Emergency
Source Voltage
|
180 Volts
|
75% Fixed
|
70 to 98%
|
70 to 98%
|
Frequency
|
60Hz
|
50 or 60 Hz
|
50 or 60 Hz
|
50 or 60 Hz
|
Pick up Emergency Source
Frequency
|
57Hz
|
95% Fixed
|
90 to 100%
|
90 to 100%
|
Drop out Emergency
Source Frequency
|
54Hz
|
85% Fixed
|
85 to 98%
|
85 to 98%
|
Normal Over Voltage Trip
|
N/A
|
N/A
|
102 to 115%
|
102 to 115%
|
Emergency Over Voltage
Trip
|
N/A
|
N/A
|
102 to 115%
|
102 to 115%
|
Normal Over Frequency
Trip
|
N/A
|
N/A
|
102 to 115%
|
102 to 115%
|
Emergency Over Frequency
Trip
|
N/A
|
N/A
|
102 to 115%
|
102 to 115%
|
Pick up Normal Source
Frequency
|
N/A
|
N/A
|
90 to 100%
|
90 to 100%
|
Drop out Normal Source Frequency |
N/A
|
N/A
|
85 to 98%
|
85 to 98%
|
Normal & Emergency Voltage Unbalance |
N/A
|
N/A
|
Yes
|
Yes
|
Time Delay Settings | 185 | 300 | 4000 | 7000 |
Override Normal Source Momentary Outage |
3 Seconds
|
1 or 3 Seconds
|
0 to 6 Seconds
|
0 to 6 Seconds
|
Transfer to Emergency |
15 Seconds
|
0 or 5 Minutes
|
0 to 60 Minutes
|
0 to 60 Minutes
|
Re-transfer to Normal Utility Power Loss Mode |
5 Minutes
|
1 Sec. to 30 Mins.
|
0 to 60 Minutes
|
0 to 60 Minutes
|
Engine Cool Down |
1 Minute
|
5 Minutes
|
0 to 60 Minutes
|
0 to 60 Minutes
|
Override Emergency Source Momentary Outage |
15 Seconds
|
4 Seconds
|
0 to 60 Minutes
|
0 to 60 Minutes
|
Emergency Exerciser |
14 Day
|
7 Day
|
Programmable
|
Programmable
|
Indication and Controls | 165 | 300 | 4000 | 7000 |
Load Connected to Normal |
Yes
|
Yes
|
Yes
|
Yes
|
Load Connected to Emergency |
Yes
|
Yes
|
Yes
|
Yes
|
Normal Source Available |
Yes
|
Yes
|
Yes
|
Yes
|
Emergency Source Available |
Yes
|
Yes
|
Yes
|
Yes
|
Transfer Test Switch |
Yes
|
Yes
|
Yes
|
Yes
|
Terminals for Remote Transfer Control |
N/A
|
Std.
|
Std.
|
Std.
|
By-pass Time Delay |
Yes
|
Yes
|
Yes
|
Yes
|
Transfer Inhibit |
N/A
|
Yes
|
Yes
|
Yes
|
In-Phase Monitor |
N/A
|
Yes
|
Yes
|
Yes
|
Load Disconnect Contacts with Time Delay |
N/A
|
Std.
|
Optional
|
Optional
|
Event Log |
N/A
|
N/A
|
Yes
|
Yes
|
Power Manager |
N/A
|
N/A
|
Optional
|
Optional
|
Transfer Controls Lock Out |
N/A
|
N/A
|
Yes
|
Optional
|
Enclosures | 185 | 300 | 4000 | 7000 |
Type 1 |
Yes
|
Yes
|
Yes
|
Yes
|
Type 3R |
Yes
|
Yes
|
Yes
|
Yes
|
Type 4 |
N/A
|
Yes
|
Yes
|
Yes
|
Type 4X |
N/A
|
Yes
|
Yes
|
Yes
|
Type 12 |
N/A
|
Yes
|
Yes
|
Yes
|
Connectivity | 185 | 300 | 4000 | 7000 |
RS-485 Serial |
N/A
|
Yes
|
Yes
|
Yes
|
Ethernet |
N/A
|
Yes
|
Yes
|
Yes
|
Modbus®
|
N/A
|
N/A
|
Yes
|
Yes
|
Monitoring and Control
via ASCO®
Products
|
N/A
|
Yes
|
Yes
|
Yes
|
Accessories | 185 | 300 | 4000 | 7000 |
Optional Accessories
|
Limited
|
Limited
|
Limited
|
Extensive
|