This is a new pop-up window on top of your GeneratorJoe browser window.  CLICK TO CLOSE WINDOW

Series 300 Automatic & Manual - Dimensions and Shipping Weights - UL Type 1 Enclosure

(Dimensional data is approximate and subject to change. Certified dimensions available upon request)

Switch Rating Amps

Phase Poles

Neutral Code

Dimensions, In. (mm)3

Shipping Weight Lb. (kg)4

Width

Height

Depth

30,70,100,104

2

A

17 1/2 (445)

31 (787)

11 5/8 (295)

67 (31)

2

B

17 1/2 (445)

31 (787)

11 5/8 (295)

70 (32)

3

A

17 1/2 (445)

31 (787)

11 5/8 (295)

70 (32)

3

B

17 1/2 (445)

31 (787)

11 5/8 (295)

73 (33)

150, 200

2

A

17 1/2 (445)

31 (787)

11 5/8 (295)

69 (32)

2

B

17 1/2 (445)

31 (787)

11 5/8 (295)

72 (33)

3

A

17 1/2 (445)

31 (787)

11 5/8 (295)

72 (33)

3

B

17 1/2 (445)

31 (787)

11 5/8 (295)

75 (34)

225, 260, 400

2

A

18 (457)

48 (1219)

13 (330)

117 (53)

2

C

18 (457)

48 (1219)

13 (330)

125 (57)

3

A

18 (457)

48 (1219)

13 (330)

125 (57)

3

C

18 (457)

48 (1219)

13 (330)

133 (61)

600, 800, 1000

2

A

34 (864)

72 (1829)

20 (508)

400 (182)

2

B

34 (864)

72 (1829)

20 (508)

420 (192)

3

A

34 (864)

72 (1829)

20 (508)

420 (192)

3

B

34 (864)

72 (1829)

20 (508)

446 (203)

1200

2

A

38 (965)

87 (2210)

24 (610)

685 (312)

2

B

38 (965)

87 (2210)

24 (610)

705 (321)

3

A

38 (965)

87 (2210)

24 (610)

705 (321)

3

B

38 (965)

87 (2210)

24 (610)

734 (333)

1600, 20001

3

A

38 (965)

87 (2210)

24 (610)

955 (433)

3

B

38 (965)

87 (2210)

24 (610)

1005 (455)

2600, 30002

3

A

38 (965)

91 (2311)

60 (1524)

1395 (633)

3

B

38 (965)

91 (2311)

60 (1524)

1460 (663)

Notes:
  1. Unit is designed for top cable entry of emergency & load and bottom entry of normal. A cable pull box is also available for all top or bottom cable access when required (optional Accessory Kit #K609027).
    Not required for type 3R, 4 &12 enclosures where available

  2. Enclosures for 2600, 3000 amps are free-standing with removable top, sides & back. >For Type 3R, 4 & 12 dimensions, add the following values to the Type 1 dimensions:
    a) 30, 70, 104, 150, 200A - add 1.5 in. (38 mm) to the height.
    b) 400A - add 1.5 in (38mm) to the depth.
    c) 1200A - type 4 & 12 not available - use 1600 amp switch
    d) 1600A - add 3 in. (76 mm) to the height and 10 in. (253 mm) to the width.
    e) 2000, 2600, 3000A - Type 4 & 12 not available. (Consult GeneratorJoe.  Write to [email protected])  Type 3R add 4.68 in (118 mm) to the height, add 2.0 in (51 mm) to the width and add 13 in (329 mm) to the depth.

  3. For Type 3R, 4 & 12 weights, add the following values to the Type 1 weights:
    a) 30, 70, 104, 150, 200A - add 15 lbs. (6.8 kg).
    b) 400, 600, 800, 1000A - add 40 lbs. (18.1 kg).
    c) 1600A - add 60 lbs. (27 kg).
    d) 2000-3000A - Type 4 & 12 not available. (Consult GeneratorJoe.  Write to [email protected])

  4. When temperatures below 32° F can be experienced, special precautions should be taken, such as the inclusion of space heaters, to prevent condensation and freezing of this condensation. This is particularly important when environmental enclosures (Type 3R, 4 & 12) are ordered for installation outdoors. See page optional accessories for space heater options (acc. 44A and 44G).

  5. All Series 300 switches are furnished with a solid neutral plate (unless switched neutral configuration is specified) and terminal lugs. Specify "A" in catalog number to order a neutral plate on the series 386 switches.

 
Series 300 & 386 External Power Connections

Sizes UL-Listed Solderless Screw-Type Terminals

Switch Rating

Ranges of AL-CU Wire Sizes   (Copper Only, Unless Specified)

30, 70, 100, 104

One #14 to 2/0 AWG

150

One #8 to 3/0 AWG

200

One #8 to 3/0 AWG CU Only

225, 260, 400

Two 1/0 AWG to 250 MCM or One #4 AWG to 600 MCM

600

Two 1/0 AWG to 600 MCM

800, 1000, 1200

Four 1/0 600 MCM

1600, 2000

Six 1/0 600 MCM

2600

Twelve 3/0 600 MCM

3000

Twelve 3/0 600 MCM

Copyright © 1996-2019 GeneratorJoe Inc. & GeneratorJoe®. All Rights Reserved. -  © Copyright 1996-2016 ASCO Power Technologies

This is a new pop-up window on top of your GeneratorJoe browser window.  CLICK TO CLOSE WINDOW