Dimensional Data and Shipping Weights - Series 7000 Soft Load

 

Dimensional Data Series 7000 Soft Load

Closed Transition Soft Load Transfer Switch Dimensions

Switch Rating
amps

Poles

Width
inches (mm)

Height
inches (mm)

Depth
inches (mm)

Enclosure UL Type 1

(Consult ASCO for Type 3R dimensions)

150, 260, 400

3 or 3 with neutral C

30 (762)

63 (1600)

17-1/2 (445)

600, 800, 1000

3 or 3 with neutral C

34 (864)

72 (1829)

20 (508)

1200

3 or 3 with neutral B

38 (965)

87 (2210)

23 (584)

1600, 2000

3 or 3 with neutral B

38 (965)

91 (2311)

48 (1219)

3000

3 or 3 with neutral B

38 (965)

91 (2311)

60 (1524)

4000

3 or 3 with neutral C

46 (1168)

91 (2311)

72 (1829)

         

Bypass-Isolation Soft Load Transfer Switch Dimensions

Switch Rating
amps

Poles

Width
inches (mm)

Height
inches (mm)

Depth
inches (mm)

Enclosure UL Type 1 (Consult ASCO for Type 3R dimensions)

150, 260, 4001, 5

3 or 3 with neutral C

28-1/2 (724)

74 (1880)

19 (483)

600, 8002

3 or 3 with neutral B/C

36 (914)

90 (2286)

22 (559)

1000, 12003

3 or 3 with neutral B

38 (965)

91 (2311)

60 (1524)

1600, 20003

3 or 3 with neutral B

38 (965)

91 (2311)

60 (1524)

30003

3 or 3 with neutral B

38 (965)

91 (2311)

72 (1829)

40004

3 or 3 with neutral C

96-1/2(2451)

91 (2311)

72 (1829)

Note:
  1. Handles extend 3-1/2 inches (89mm).
  2. Handles extend 6-1/4 inches (159mm). Standard enclosure for 600-800 amp sizes are suitable for top cable entrance only. Specify 44" wide enclosure for bottom cable entry.
  3. Recommended clearance to enclosure: 3 feet (914mm) from rear, 4 feet (1219mm) from front (25 inches required for transfer switch drawout).
  4. For 4000 amp size, ATS and Bypass sections can be reversed; contact ASCO. Recommended clearance to enclosure: 3 feet (914mm) from rear, 5 feet (1524mm) from front (3 feet required for transfer switch rollout).
  5. Dimensions for 400 amp. 7A DTB and 7N DTB with neutral code B are 36 (914)W x 90 (2286)H x 22 (559)D.
 

Shipping Weights Series 7000 Soft Load

Closed-Transition Soft Load Transfer Switch Shipping Weights

Switch Rating
amps

Poles

Enclosed
lb (kg)

150, 260, 400

3

205 (93)

150, 260, 400

3 with C

213 (96)

600, 800, 1000

3

510 (231)

600, 800, 1000

3 with B

540 (244)

1200

3

800 (362)

1200

3 with B

830 (375)

1600, 2000

3

1410 (612)

1600, 2000

3 with B

1460 (660)

3000

3

1680 (762)

3000

3 with B

1745 (792)

4000

3

2640 (1193)

4000

3 with C

2740 (1238)

Bypass-Isolation Soft Load Transfer Switch Shipping Weights

Switch Rating
amps

Poles

Enclosed
lb (kg)

150, 260, 400

3

350 (158)

150, 260, 400

3 with C

360 (163)

600, 800

3

710 (322)

600, 800

3 with B/C

750 (340)

1000, 1200

3

2265 (1027)

1000, 1200

3 with B

2485 (1127)

1600, 2000

3

2495 (1132)

1600, 2000

3 with B

2675 (1213)

3000

3

2790 (1266)

3000

3 with B

3420 (1552)

4000

3

6300 (2858)

4000

3 with C

6900 (3130)

Note: *
Export shipments may require a wooden box. Contact ASCO for weights and dimensions. Consult ASCO for Type 3R shipping weights.
 
ASCO 7000 Series
Closed-Transition Soft Load Transfer Switch Terminals
Sizes of UL Listed Solderless Screw-Type Terminals for External Power Connections

Switch Rating
amps

Max No. of Conductors
per Terminal

Range of AL-CU
Conductor Sizes

150, 260, 400

One

#4 AWG to 600 MCM

600

Two

#1/0 AWG to 600 MCM

800 - 1200

Four

#1/0 AWG to 600 MCM

1600 - 2000

Six

#1/0 AWG to 250 MCM

3000 - 4000

Twelve

#1/0 AWG to 600 MCM

 
ASCO 7000 Series
Bypass-Isolation Soft Load Transfer Switch Terminals
Sizes of UL Listed Solderless Screw-Type Terminals for External Power Connections

Switch Rating
amps

Max No. of Conductors
per Terminal

Range of AL-CU
Conductor Sizes

150, 260, 400

One

#4 AWG to 600 MCM

600 - 800

Three

#2 AWG to 600 MCM

1000 - 1200

Four

#1/0 AWG to 250 MCM

1600 - 2000

Six

#1/0 AWG to 600 MCM

3000

Eight

#1/0 AWG to 600 MCM

4000

Twelve

#1/0 AWG to 600 MCM

Copyright © 1996-2019 GeneratorJoe Inc. & GeneratorJoe®. All Rights Reserved. -  © Copyright 1996-2016 ASCO Power Technologies