This is a new pop-up window on top of your GeneratorJoe browser window.  CLICK TO CLOSE WINDOW

AIR CONDITIONING & HEAT PUMP LOADS - TYPICAL

SIZE BTU HP Running Load Starting Load

Running
kW

Amps @
240 Volts 1 Phase

Amps @
208 Volts 3 Phase

Amps @
480 Volts 3 Phase

Starting
kW

Amps @
240 Volts 1 Phase

Amps @
208 Volts 3 Phase

Amps @
480 Volts 3 Phase

1 Ton

12,000

1

1

5

3

1

3

25

17

7

2 Ton24,0002210736503314

3 Ton

36,000

3

3

15

10

4

9

75

50

22

4 Ton48,0004420136121006729

5 Ton

60,000

5

5

25

16

7

15

125

83

36

7.5 Ton85,0007.57.53724111718812554

10 Ton

120,000

5 (x2)

10

49

33

14

15

125

83

36

10 Ton120,00010104933142018816772

15 Ton

180,000

7.5 (x2)

15

74

49

21

17

125

125

54

15 Ton180,000151574492130250250108

20 Ton

240,000

10 (x2)

15

98

65

28

20

188

167

72

20 Ton240,0002020n/a652840500333144

25 Ton

300,000

25

25

n/a

82

35

50

625

416

180

30 Ton360,00015 (x2)30n/a984230375250108

30 Ton

360,000

30

30

n/a

98

42

60

750

500

217

40 Ton480,00020 (x2)40n/a1315740500333144

40 Ton

480,000

40

40

n/a

131

57

80

1000

666

289

50 Ton480,00025 (x2)50n/a1637150625416180

50 Ton

480,000

50

50

n/a

163

71

100

1250

833

361

 

Copyright © GeneratorJoe Inc. & GeneratorJoe®. All Rights Reserved.