Fuel Pipe Sizing

Natural Gas
kW .5" .75" 1" 1.25"1.5"2"2.5"3"
1.8 125 - - -----
2.5 70 125 - -----
4 30 100 - -----
5 10 70 - -----
7 - 40 200 820----
7.5 - 40 200 500----
8 - 20 100 425----
 10 - 20 85 370800---
12 - 10 65 275600---
13 - 10 50 245545---
16 - - 40 190425---
20 - - 20 115265

950

--
25 - - 10 75180

660

--
30 - - - 601505651380-
35 - - - 3595370915-
40 - - - 2575315790-
50 - - - 1050220560-
60 - - - -25145390115
70 - - - -575225710
80 - - - --65195630
100 - - - --40140460
130 - - - ---50215
150 - - - ---30150
 

LP Vapor (LPV)

kW .5" .75" 1" 1.25"1.5"2"2.5"3"
7 110 165 570 -----
 10 50 70 255 1000----
13 20 45 170 690----
16 15 30 130 540----
20 - 15 80 340745---
25 - - 50 235520---
30 - - 40 200445---
35 - - 20 1252901030--
40 - - 15 107250890--
50 - - - 70170635--
60 - - - 451154451095-
70 - - - 2060260660-
80 - - - 1550230590-
100 - - - -301654301305
130 - - -  -70205660
150 - - - - - 45 150 490

Note:
– Table values are maximum pipe run in feet.
– Pipe sizing is based on .5" H2O pressure drop.
– Sizing includes a nominal number of elbows and tees.
– Please verify adequate service and meter sizing.

  Copyright © 1996-2019 GeneratorJoe Inc. & GeneratorJoe®. All Rights Reserved.