EXTREME CAUTION:
Please be advised that failure
to anchor the PTO Driven Alternator may cause the unit to flip
and inflict severe injury and/or damage to the operator and/or
surrounding structure and equipment. It is highly recommended
that the alternator be bolted down and securely anchored to
a concrete slab that has been well reinforced with steel re-bar.
Friesen Electric Inc. will not be liable for any injury or damage
incurred as a result of negligence regarding installation.
Follow the instructions in the owner's manual specifically when
putting this alternator into service.
|
IMPORTANT:
All standby power plants including
Tractor Driven Alternators should be periodically exercised.
For proper maintenance of your Tractor Driven Alternator, it
should be operated for one hour carrying rated load at least
twice a year. This will assure that your alternator is
in operating condition and ready for use when an emergency condition
develops.
|
TRACTOR DRIVEN ALTERNATORS
TABLE OF CONTENTS
- Introduction
-
Operating the Alternator
-
Maintenance Requirements
-
What is a Static
Excited Type Generator?
- PTO
Alignment
-
Operation of Tractor
Driven Alternators
-
Procedure for Use
-
Service Diagnosis
-
Testing of Rectifier Assembly
-
Handling Procedure for Rectifiers
- Sticky
Brushes
-
Build Up of the Excitation
Field
-
Field Check of
Armatures
-
Testing a Field Circuit
-
Lubricant Cross Reference Chart
INTRODUCTION:
The words generator & alternator are
used interchangeably but have the same meaning. This manual
covers standby generators driven by the power take-off of a farm tractor.
These generators use a static excitation system which will be discussed
in later paragraphs of this manual. All generators are carefully inspected,
tested, and packaged for shipment at the factory. The generator should be
unpacked as early as possible upon receipt and inspected for damage which
may have occurred during shipment. Any damage noted should be promptly reported
to the carrier in order that a claim can be filed to recover the cost of
the damage. If at all possible, this damage should be noted on the freight
bill at the time of delivery. If the damage appears to be of a major nature,
the generator should not be operated until the fault has been corrected.
Tractor driven generators are designed
to deliver voltage and current similar to that of the normal power line.
Equipment that can be operated on normal power can also be operated by the
generator, provided that the capacity of the generator is not exceeded.
It should be remembered that the power line, for all practical purposes,
is backed by an unlimited generator.
When not in use the generator should
be stored in a clean dry location. All types of mechanical equipment suffer
from long periods of storage without use. The generator should be used at
frequent intervals at some convenient time. By this procedure deterioration
will be prevented and any possible fault will be noted before any emergency
condition develops.
OPERATING
THE ALTERNATOR
A double throw manual transfer switch
must be used with a standby generator. The load, connected to the normal
terminals of the transfer switch, is energized by the normal power line
when the switch is in the normal position. The generator, connected to the
emergency terminals of the switch, furnishes power when the switch is in
the emergency mode position. When the normal power fails, the generator
is attached to the tractor by means of the power take-off shaft.
Start the tractor and adjust the speed
until the pointer of the voltmeter on the generator panel registers on the
high side of the green portion of the colour band.
Check the connected load to assure that
all heavy electrical equipment is disconnected.
Move the transfer switch handle to the
emergency position connecting the load to the generator.
Switch on all required electrical equipment
within rated capacity of the generator maintaining tractor speed to cause
the voltmeter to remain in the green portion of the colour band.
If the circuit breaker of the generator
control panel trips during operation, the connected load is greater than
the rated generator capacity.
Reduce the load by disconnecting any
non-essential equipment during emergency conditions.
After a short delay, indicating that
the power restoration is not temporary, the transfer switch can be returned
to the normal position and the tractor drive generator shut down.
After the load has been returned to normal
power, normal precautionary measures should be made for protection of the
tractor drive generator. If the generator is mounted on an off-highway trailer,
such as the Winpower TD-M/73, it should be stored in a barn or machine shed
in a dry and clean location. The generator should be covered with a tarpaulin
to prevent the entrance of dust, chaff, and/or moisture. Generators installed
in a permanent location should be mounted on a concrete base of at least
3" reinforced slab. Some provision should be made for a water and dust-tight
cover to remain in place during stand-by conditions. A simple frame enclosure
including doors for connecting to the power take-off and for ventilation
is a very worthwhile provision. A typical weather protected installation
is shown in Figure 1.
MAINTENANCE
REQUIREMENTS
-
Maintain proper oil level in the
PTO gear case. See the list attached for lubricants. Do not overfill,
maintain level to the small pipe plug approximately 4" from the bottom
of the gear case on the gear case cover.
-
Make frequent inspection of the collector
ring brushes. Brushes should move freely in the brush holders. When
lifted from the surface of the collector ring by the brush shunt, and
released, the brush should snap back in contact with the collector ring.
Inspect brushes for wear. A brush that does not fill at least two thirds
of the brush holder should be replaced.
-
Inspect for loose or broken wiring
connections. Make sure that wiring connections are not loosened at the
brush holder.
-
Do not allow dirt or chaff to collect
in the interior of the generator or the ventilation openings. Inspect
for indication of the entrance of mice into the generator. The inlet
and outlet openings are louvered, but possible damage to the louvers
could occur. Mice can destroy the generator winding.
WHAT IS A STATIC EXCITED TYPE GENERATOR?
The word "static" means without motion;
thus, the term "static excited" means that the excitation current for the
field is supplied without the use of outmoded rotation type of excitation.
Commutators and commutator brushes with the inherent problems of commutation
and maintenance are not used.
In the FRIESEN static excited alternator,
the alternating current output of the generator is rectified by means of
a full-wave silicon diode bridge. Resulting direct current is used to supply
the stationary field coils.
There is also a circuit in the alternator
excitation system to maintain a relatively constant voltage as the load
is varied.
The excitation circuit uses only one
rectifier bridge. In this system the divided primary of the current transformer
is connected in series with load lines. The secondary output of this transformer
is then connected to the shunt field and is also controlled by a reactor
in series with one connection to the AC side of the bridge. The reactor
serves to control the energy at no load, which reduces as load is added
and also maintains stable voltage output by varying the field strength.
The use of the current transformer provides
not only a means for variation of field strength for normal loading, but
also a means for "forcing the field" during sudden momentary overloads such
as are encountered in the starting of motors. This means the intermittent
capacity of the alternator can be increased to the higher rating indicated
in the model designation.
PTO ALIGNMENT
Position the alternator in such a manner
that the power takeoff shaft is as near to direct line in all directions
as possible. This will increase the life of the power takeoff shaft, reduce
ware on bearings of both the power takeoff and the alternator, and reduce
vibration. The maximum angle from a straight line should not exceed 10°.
For the nominal power takeoff shaft length of 42", 10° is equal to 8" misalignment.
For extended distance the maximum misalignment would increase 2" for each
foot. For Example: For a 6' PTO shaft the maximum misalignment is 12" from
a straight line.
OPERATION OF TRACTOR DRIVEN ALTERNATORS
When the alternator is not in use it
must be maintained in a clean and dry condition. The inside of the panel,
frame, and air inlet and outlet must be free from dirt and chaff.
When connection is made at the meter
pole, a double throw manual transfer switch must be used. Normal power is
connected to the top, the load at the centre, and the alternator at the
bottom of the switch. Warranty is void if a transfer switch is not used.
PROCEDURE
FOR USE
-
Set the main circuit breaker on the
alternator panel to "off."
-
Connect the power take-off shaft
securely to the alternator and the tractor. Position as near to a straight
line as possible.
-
Adjust power take-off speed to maximum
then back down to maintain the voltage indicator in the green portion
of the color band.
-
Place plug in receptacle. Place transfer
switch in the emergency position.
-
Place the load circuit breaker in
the "on" position. If the breaker trips, check for short circuit or
grounded connection in the load cable to the double throw switch. A
breaker that trips from overload or short circuit must be reset by moving
to "off" before re-closing.
-
Keep meter in the green by adjusting
tractor speed.
-
The return of normal power will be
indicated by the lamp on the front of transfer switch; applicable only
when the transfer switch is equipped with indicating lamps. After
sufficient time to assure that power restoration is not temporary, return
the transfer switch to normal power.
-
Place the alternator circuit breaker
in "off" position. Do not remove plug before opening the breaker.
-
Slowly reduce power take-off speed
to a minimum and disengage the power take-off. Some tractors have
a brake on the power take-off which stops the shaft instantly.
Stopping the alternator rotor instantly from rated speed may result
in a broken shaft.
-
Exercise PTO alternator for one
hour carrying rated load at least twice a year.
SERVICE DIAGNOSIS
This section contains
information on how to trouble shoot for
low output voltage,
high output voltage,
excessive heating,
no output voltage,
defective armatures,
unsteady voltages,
and slow voltage buildup.
LOW OUTPUT VOLTAGE
Possible Cause
|
Remedy
|
Low speed
|
Check for overload
on the engine or tractor.
Defective governor.
Check governor spring tensions, tight or defective throttle
levers and joints.
Defective engine
(see engine check list).
|
High line loss.
Indicated by lower voltage at load than at generator terminals |
Increase size of
line wiring. Might also be the result of loose connection
which will be indicated by excessive heating at the loose connections. |
Shorted or grounded
field coil. In some cases one coil only, that is shorted
or grounded, will reduce voltage to approximately one half of
rating. |
See information for
testing field circuits.
|
HIGH OUTPUT VOLTAGE
Possible Cause |
Remedy |
Excessive speed. |
Check governor
linkage, spring tensions, etc. Governor linkage
must be free from dirt and gum. |
EXCESSIVE HEATING
Possible Cause
|
Remedy
|
Clogged ventilating inlet and/or outlet. |
Clean screens, make sure interior of generator is unobstructed. |
NO OUTPUT VOLTAGE
Possible Cause
|
Remedy
|
Poor brush contact: Brushes tight in holder. |
Clean brush
holder. Brush should move freely in holder. |
Weak brush spring tension. |
Brush spring
tension should snap brush into contact with ring when lifted
and released. |
Film on collector rings caused by corrosive or dirty atmosphere. |
Clean rings
with fine sandpaper during rotation of armature.
Caution: Tape sandpaper to stiff cardboard
for safety. |
Defective rectifier bridge (see method
of
checking bridge) |
Replace defective
bridge assembly. |
Open field circuit (see illustration for
method for checking, Figure
2) |
Replace open
coil(s) or repair if open connection is in the connecting loads. |
Grounded or shorted field coil(s). |
Replace grounded
coil(s) and insulation or repair damage. |
Loss of residual
magnetism. This is a condition brought about by some unusual
condition. It will usually occur after disassembly of
the field frame. |
Restore magnetism.
|
DEFECTIVE ARMATURE
Possible Cause
|
Remedy
|
Shorted winding. This can be identified by the use of
a "growler" at a competent rewinding shop. |
Replace the armature. (Include generator model and serial
number on the order). |
Grounded armature. Check winding by test lamp or high
potential tester from collector rings to shaft. |
Replace the armature. (Include generator model and serial
number on the order). |
Open armature circuit. Measure circuit between rings with
an ohmmeter. Should have a circuit between any pair of
rings |
Replace the armature. (Include generator model and serial
number on the order). |
VOLTAGE UNSTEADY
Possible Cause
|
Remedy
|
Loose connection, probably at rectifier. |
Tighten with pliers. |
SLOW VOLTAGE BUILDUP
Possible Cause
|
Remedy
|
Slow voltage buildup, or no voltage buildup, unless load is
applied. |
See below. |
Excessive air gap between armature and field poles. |
Shim all poles est. 0.007. |
Not enough air
gap in choke.
|
Remove top part
of choke and install thickness of a regular piece of paper until
voltage builds up in 3 to 5 seconds or 260V no load on 120/240V
unit. Replace top of choke and tighten the bolt.
Loose bolts will cause chatter and unstable voltage. |
TESTING OF RECTIFIER ASSEMBLY
Remove the lead from the positive ( +
) terminal and one of the leads going to AC terminal of the bridge.
-
Connect black lead of meter to positive
( + ) terminal of bridge and red lead to one of the AC terminals of
bridge. Meter should read about 20 Ohm.
-
Now, reverse the lead on bridge terminals.
Meter should read open circuit or infinite resistance.
-
Connect black lead of meter to (
+ ) terminal and red lead to other AC terminal of bridge. Meter should
read about 20 Ohm.
-
Now reverse the leads on bridge terminals.
Meter should read open circuit or infinite resistance.
-
Connect red lead of meter to ( -
) terminal of bridge and black lead to one of the AC terminals of the
bridge. Meter should read about 20 Ohm.
-
Reverse the leads and you should
read infinite resistance.
-
Connect red lead of meter to ( -
) terminal of the bridge and black lead of meter to other AC terminal
of the bridge. Meter should read about 20 Ohm.
-
Now reverse the leads and you should
observe infinite reading on your meter.
All eight steps are described for a good
bridge.
A shorted diode will give zero resistance
reading in both directions.
A low resistance reading of 2 Ohms or
so will show leakage current and diode should be replaced.
An open diode will give a high resistance
(infinite) reading in both directions.
HANDLING PROCEDURE FOR RECTIFIERS
(Diodes & Bridge Assemblies)
-
Rectifiers should be handled in a
manner which avoids the possibility of sudden shocks being applied,
such as those encountered in dropping from a work bench to a hard floor.
Damage done to the rectifier by such shocks may not be detected by subsequent
testing, yet may cause poor system reliability.
-
Any lead trimming or forming operations
should be done with care to avoid damaging the leads or the glass header
seals.
-
Leads should never be bent or twisted.
If lead forming is necessary the lead should be supported so that no
bending occurs closer than 1/8 inch to the rectifier body, and that
header seals are not fractured or broken. If this seal is broken, it
removes mechanical support for the lead and allows entry of moisture
into the rectifier, almost assuring early failure.
-
Care must be taken during all soldering
operations. It is unsafe to exceed the general specification to which
diodes are tested for solder ability. This is 10 ±2 seconds at a temperature
of 230°C +5°C at a point 1/16" ±1/32" from the diode body. This is not
as restrictive as it may sound, since 230°C is 446°F and 60/40 solder
melts at 375°F, and with proper procedure & soldering tools a solder
joint can be made in 4 to 7 sec. Also, solder joints are almost never
made this close to the diode body. Heat sinks, such as a pair of needle
nose pliers or alligator clips, can be attached to the lead between
the solder joint and the diode body to further reduce the possibility
of heat damage.
Also, precautions should be taken to
prevent solder or flux bridging which causes a conductive path across the
case of the rectifiers. As a precaution all flux should be removed by using
alcohol and a small brush. Pay particular attention to assure that glass
header seals are free of all flux.
STICKY BRUSHES
Brushes must move freely in the brush
holders to maintain contact to the slop rings. The field circuit begins
at the brushholders. If the brush does not maintain contact to the ring,
or if a film has developed on the ring from lack of use and maintenance,
there will be no current in the field coils; consequently, the field strength
will not increase from the low residual value resulting in lack of voltage
buildup. The cause in both cases is usually lack of maintenance and improper
storage.
BUILD UP OF THE EXCITATION FIELD
Occasionally an alternator will seem
to be defective as there is no indication on the voltmeter on start up.
This will sometimes be caused by a too careful increase in power take-off
speed. Rated speed is not actually reached. The better procedure is to adjust
to maximum, then back down to maintain the indication in the "green" portion
of the colour band.
When repairs have been made or the alternator
has not been used for a long period it may be necessary to "flash the field."
An inexpensive tool using a small step-down transformer is the best means
for this purpose. It has a nominal input of 125V, 25VV secondary and 2 ampere
rating. Avoid the use of a variable transformer. Reversal of power line
and alternator ground may cause damage.
With the alternator operating, plug the
transformer into a wall outlet and insert the prods into the 125V outlet
on the alternator panel. Remove at once when an indication is shown on the
voltmeter.
FIELD CHECK OF ARMATURES (Tractor
Drives)
-
Instrument required -- Volt-Ohm Meter.
Set on Ohm X1 scale.
-
Check Ohm Meter by touching leads
together. Reading should be zero.
-
Lift all brushes form armature that
is to be checked.
-
First check to find out if
armature windings are grounded (most probable).
a. Connect one lead of
Ohm Meter to ground.
b. Touch other lead to
each ring. Meter should stay at infinite (not move).
c. If reading is indicated, armature
is grounded and should be replaced.
d. If armature has commutator, it
should not indicate ground.
-
Second check to find out if
armature windings are open.
Symptom: when generator was running
no voltage on one line to neutral, or on 115V unit no voltage. Lift
all brushes.
a. Armature 3 Rings, 1Ø or
3Ø, 3 Wire
Connect one ohm meter lead to Ring 1. Touch other lead
to Ring 2. Meter should read Zero or very low. Then touch
lead to Ring 3. Meter should read Zero. Winding is open if reading
is infinite.
b. Armature 4 Rings, 3Ø, 4 Wire
Connect one ohm meter lead to Ring 1 Touch other lead to
Ring 2 Reading should be near zero Touch other lead to Ring
3 Reading should be near zero Touch other lead to Ring 4 Reading
should be near zero
c. Armature 4 Rings, 1Ø
This armature has two windings One starting on Ring 1 ending
on Ring 2, and one starting on Ring 3 ending on Ring 4.
Connect ohmmeter one lead to Ring 1. Other lead to Ring
2, meter should read near zero. Other lead to Ring 3, meter
should read infinite. Other lead to Ring 4, meter should read
infinite. Connect one lead to Ring 3. Other lead to Ring
4, meter should read near zero. Other lead to Ring 1, meter should
read infinite. Other lead to Ring 2, meter should read infinite
FIGURE 2
NOTE: Fields alternate "straight" and "crossed" to provide
proper polarity. When ordering replacement coils be sure to include Model,
Type, and Serial Number.
TESTING
A FIELD CIRCUIT
Disconnect
field leads F1 and F2
Measure resistance
of entire field circuit as shown in Figure
2. A resistance of less than the range
shown on the table indicates a shorted coil. The defective coil can be identified
by measuring the resistance of the individual coils. A coil with an appreciable
lower resistance has shorted turns.
A reading of no deflection or very little
deflection of the meter pointer indicates a defective coil or broken interconnection.
Inspect all interconnecting wires for tight and un-corroded connection.
Each coil should measure approximately ¼ of the total specified resistance.
A very high resistance indicates broken internal wires.
A grounded field can be identified by
connecting one ohmmeter lead to one field lead and touching the other to
an unpainted spot on the field ring. Make sure that none of the coil leads
are in contact with the ring. A grounded field can usually be corrected
by repairing the insulation once the grounded point or points are located.
NOTE: Whenever the field
could have been removed and/or replaced, the field must be re-energized.
LUBRICANT CROSS REFERENCE CHART
(For Chain Driven Units)
Manufacturer |
Description |
Alemite |
HD Gear Oil No.
3 |
Allube (Far-Best
Corp.) |
Moly-Shield IGO
80 |
America Lubricants
Co. (Alubco) |
Albuco Moly
Ultra-Tec
Lube, SAE 80 |
Amoco Oil Co. (Standard
Oil Co. of Indiana) |
Amogear EP1 |
Ashland Oil & Ref.
Co. |
EP Compound No.
30 |
Atlantic-Richfield
Co. |
Pennant NL S-315 |
Bel-Ray Co., Inc. |
Bel-Ray 100 Gear
Oil #50 |
Boron Oil Co. |
Gearep 80 |
Brooks Oil Co. |
Brooks L-40 |
Cato Oil and Grease
Co., Inc. |
Universal 2105 Gear
Lub 80 |
Champlin Petroleum
Co. |
MGX #3 |
Chevron Oil Co.
(Standard Oil Co. of California |
Chevron NL Gear
Compound 68 |
Cities Service Oil
Co. |
Citgo EP Compound
55 |
Continental Oil
Co. |
Milgear L50 |
DuBois Chemicals |
MPO-30 |
Exxon Co., U.S.A. |
Spartan EP68 |
Fiske Refining Company |
APG 80 |
Georgia-Carolina
Co. |
G-C Yukol E.P. #80 |
Gulf Oil Corp. |
E.P. Lubricant 55 |
Imperial Oil & Grease
Co. |
Molub-Alloy 804 |
Kendall Refining
Co. |
Kendall NS-MP SAE
80 W |
Mobil Oil Co. |
Mobilgear 626 |
National Refining
Co. |
EP Compound No.
30 |
Parr Inc. |
1022 |
Pennwalt Corp. (Keystone
Div.) |
WG 5X |
Pennzoil Co. |
Maxol EP #1 or MP4080 |
Phillips Petroleum
Co. |
Philube ILB Gear
Oil EP-3 |
Shell Oil Co. |
OMALA 33 |
Standard Oil Co.
(Ohio) |
Gearep 80 |
Stewart-Warner Corp. |
HD Gear Oil No.
3 |
Sun Oil Co. |
Sunep 1050 |
Texaco |
Meropa 68 |
Tower Oil & Technology
Co. |
Express Gear Lube
EF |
Valvoline Oil Company |
EP compound No.
30 |
While & Bagley Co. |
Oilzum Super Gear
Oil SAE 80 EP |
Union Oil Co. of
California Western Region |
Union PB Gear Lube
50 |
Union Oil Co. of
California Eastern Region |
Union Ext. Duty
NL 50 |
United Refining
Co. |
Emblem APG Lube
ZEP (80) |
West Penn Oil Co.,
Inc. |
W/P Hi-Gear Compound
No. 1 |
|